MOTOR CIRCUIT-BREAKER TESYS GV2ME073

Product number
4321786
TeSys GV2, Circuit breaker, thermal-magnetic, 1,6...2,5A, spring terminals
TeSys GV2, Circuit breaker, thermal-magnetic, 1,6...2,5A, spring terminals. range: TeSys - product name: TeSys GV2 - device short name: GV2ME - product or component type: circuit breaker - device application: motor - network type: AC - utilisation category: AC-3 conforming to IEC 60947-4-1, category A conforming to IEC 60947-2 - breaking capacity: 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2, 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 - [Ics] rated service short-circuit breaking capacity: 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2, 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 - magnetic tripping current: 33.5 A. Benefits: Complete protection concentrated in a single product. Compact and simple to select, TeSys GV2motor circuit-breakers are only 45mm wide and are categorized according to their level of performance and functions: type of control, breaking capacity, motor protection and accessories.... Applications: - Industry, infrastructure, building, etc:, Motor control and protection, in accordance with standards IEC 947-2 and IEC 947-4-1., Easily inserted in any configuration by screw or clip-fixing onto mounting rails..

Product details

Technical specifications

Adjustment range undelayed short-circuit release33.5 ... 33.5 A
Degree of protection (IP)IP20
Depth78.2 mm
Device constructionComplete device in housing
Height101 mm
Number of poles3
Overload release current setting1.6 ... 2.5 A
Phase failure sensitivetrue
Rated operating voltage690 ... 690 V
Rated operation power at AC-3, 230 V0.37 kW
Rated operation power at AC-3, 400 V0.75 kW
Rated permanent current Iu2.5 A
Rated short-circuit breaking capacity lcu at 400 V, AC100 kA
Switch off techniqueThermomagnetic
Thermal protectiontrue

Product codes

SAPGBK024
PLC4321786
STK4321786
GTIN/EAN3389110346428
Manufacturer part numberGV2ME073
Vendor material numberGV2ME073

Basic information

Package measurements (L x W x H)112 x 85 x 55 mm
Package volume0.524 l
Package weight0.326 kg
Base uniteach
Package units1 / 20 / 320
Usage quantity
UNSPSC39121521
BrandSCHNEIDER