EFFEKTBRYTER 3P 32A KLEMME NZMB1-A32

Product number
4358977
NZMB1-A32
Komplett effektbryter, 15 ...160 A
Maks: 690 V 50/60 Hz. EN 60947
I2 = høyeste prøvestrøm
Ii = elektromagnetisk utløserstrøm
A-type = termisk/elektromagnetisk vern
M-type=termisk/elektromagn. motorvern
Rammeklemme Cu moment 9Nm
Tunnelklemme Al/Cu moment 15Nm
Bolttilkobling moment 9Nm

Ik max: Ics = Icu = 30 kA (230V)
I2: 1,3 x In
Ii: Se beskrivelse
Rammeklemme for Cu
3 - polet: NZMB1-...

Product details

Technical specifications

Rated permanent current Iu32 A
Rated voltage440 ... 440 V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz25 kA
Overload release current setting25 ... 32 A
Adjustment range short-term delayed short-circuit release0 ... 0 A
Adjustment range undelayed short-circuit release350 ... 350 A
Device constructionBuilt-in device fixed built-in technique
Integrated earth fault protectionfalse
Type of electrical connection of main circuitFrame clamp
Suitable for DIN rail (top hat rail) mountingfalse
DIN rail (top hat rail) mounting optionaltrue
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact0
With switched-off indicatorfalse

Product codes

SAPGAM432
PLC4358977
STK4358977
GTIN/EAN4015082809898
Manufacturer part number280989
Vendor material number4358977

Basic information

Package measurements (L x W x H)145 x 88 x 90 mm
Package volume1.148 l
Package weight1.035 kg
Base uniteach
Package units1 / 1
Usage quantity
UNSPSC39121600
BrandEATON