MOTOR CIRCUIT-BREAKER GV3P50

Product number
4321754
TeSys GV3-Circuit breaker-thermal-magnetic, 37…50A, EverLink BTR connectors
TeSys GV3-Circuit breaker-thermal-magnetic, 37…50A, EverLink BTR connectors. range: TeSys - product name: TeSys GV3 - device short name: GV3P - product or component type: circuit breaker - device application: motor - network type: AC - utilisation category: AC-3 conforming to IEC 60947-4-1, category A conforming to IEC 60947-2 - breaking capacity: 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2, 12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2, 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 - [Ics] rated service short-circuit breaking capacity: 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2, 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2, 50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2, 50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 - magnetic tripping current: 700 A. Benefits: .. Applications: Machine manufacturers (all segments) and control system panel builders.... Benefits: A stronger, safer, and long-term connection. Designed with the new and ingenious, EverLink* patented, power terminal system, TeSys GV3 circuit-breaker provides a more reliable connection quality: the tightening pressure applied to the cables remain stable, strong and long-lasting even under tough conditions. Common additive parts to GV2 and GV3 ranges provide simplicity and significant installation time saving.... Applications: - Industry, infrastructures, buildings: Used for motor control and protection, complying with IEC 947-2 and IEC 947-4-1 standards... *Schneider patent....

Product details

Technical specifications

Overload release current setting37-50 A
Adjustment range undelayed short-circuit release700-700 A
With thermal overload protectionyes
Phase failure sensitiveyes
Switch off techniqueThermomagnetic
Rated operating voltage690-690 V
Rated permanent current Iu50 A
Rated operation power at AC-3, 230 V15 kW
Rated operation power at AC-3, 400 V22 kW
Power loss8 W
Type of electrical connection of main circuitScrew connection
Type of control elementTurn button
Device constructionComplete device in housing
With integrated auxiliary switchno
With integrated under voltage releaseno

Product codes

SAPADV940
El number4321754
Product number4321754
GTIN/EAN3389119405409
Manufacturer part numberGV3P50
Vendor material numberGV3P50

Basic information

Package measurements (L x W x H)145 x 65 x 160 mm
Package volume1.508 l
Package weight1.008 kg
Base uniteach
Package units1 / 10 / 60 / 120
Usage quantity
UNSPSC39121521
BrandSCHNEIDER ELECTRIC
Country of OriginFR France
Customs tariff code85362000